ROOM INTEGRITY TEST
Door Fan / Leakage Test
Door fan test gas extinguishing system is applied in the places where the gas remains inside for 10 minutes, it is mandatory tests to test. Regardless of the type of gas penetrating inside, door fan tests should be applied to every room.
According to the conditions specified by the relevant standards; For the door fan test, at least 85% of the gas penetrating the environment must be present in the environment after 10 minutes. Otherwise, the site will not pass the test.
In these tests, no construction work should be left at the site and it should be done after the commissioning processes.
It is the process that only the relevant personnel is convicted of doing, after receiving a certificate of success as a result of the trainings carried out in accredited institutions for the door fan test. It should be noted that most of the gaseous chemicals used to extinguish the fire are heavier than air.
As the extinguishing gas, which starts to discharge, will rise from the ground and begin to fill the space, it will begin to leak very quickly from the low-level leak areas. Dame etc. that may cause gas leakage during the test. openings need to be closed with automation. If there are any detected openings, they should be closed with firestop materials and the test should be repeated.
The result of the test to be performed is submitted to the administration as a report according to the result report to be obtained from the related software.